Can a WL circuit breaker provide personal (5mA) or equipment (30mA) ground fault protection?


The minimum ground fault pick-up setting for WL circuit breakers is 100 amps for ground fault protection.

When ground fault sensitivity in the range of 0.5mA or 30 mA ground fault protection is required, Siemens recommends using QP, BL and, ED frame circuit breakers.