Can the MBK175A be installed in load centers that do not list this main breaker kit as in the accessory table on the wiring diagram?


If this kit is not listed on the wiring diagram by part#, check the series rating label.

If the label indicates EQ869#, the EQ8694 (MBK175A) can be field installed in panels that allow the field installation of EQ8695.