This articles details the information on the knowledge base releases for the month of April 2021.
|
3VA
|
|
- Add 3VA53,63,54,64 – Single, panel mounted 400/600A branches - solid state & thermal mag released as default
|
|
- Add 3VA53,63,54,64 – Panel mounted 400/600A mains - solid state & thermal mag released as default
|
|
- Add 40, 110, 225, 350A trip selections on ETU 3VAs, which automatically select LCD ETU and adds indication to show that LCD is selected
|
|
- Add TU Protective Parameters field to indicate LI, LSI, LSIG, etc.
|
|
|
|
Digital Meter
|
|
- Update PAC3220/4200 expansion modules to allow selection of two modules
|
|
|
|
MCCBs
|
|
- Update DAS conflict messages
|
|
- Correct drawing symbol for individually mounted 38W MCCB breaker
|
|
|
|
Panelboard
|
|
- Allow for new 30” enclosure width in IPS switchboard
|
|
|
|
Transformers
|
|
- Update section dimensions for K13 transformers
|
|
|
|
Section
|
|
- Prevent 48” & 58” deep sections when OSHPD selected
|
|
- Update 28” deep busway position to 18” from 14” from front of section to center of busway
|
|
|
|
Series Ratings
|
|
- Update to latest series available series ratings, including newest 3VA ratings
|
|
|
|
Tap
|
|
- Add selection for Ameren solar tap
|
|
|
|
WL
|
|
- Add PTs when meter plus is selected
|
|
- Correct layout error when 5000A branch with auxiliary compartment
|
|
- Select lock kit covers when WL with auto throw-over system
|
|
|
|
Utility Metering
|
|
- Allow cold sequence when Des Moines utility selected
|
|
- Automatically select PTs when required on Ameren utility compartments
|
|
|
|
Technical
|
|
|
|
|
|
|
|
Introducing New P3 Features Specifications:
|
|
- Large unit space mounted breakers can be selected in P3 are: 225A QRs, 150A 3VA61, 250A 3VA62, 250A 3VA52.
|
|
- New P3 design now offers more quantity large unit space mounted branch breakers: Up to quantity (12) large unit space mounted breakers can be allowed in P3 where only (6) is allowed currently.
|
|
- 30” wide new vented enclosure is required if large breaker quantity is > 6 and up to (12).
|
|
- 30” wide new vented enclosure is required when 600A horizontal mounted 3VA main and or 600A 3VA sub-feed branch is selected in P3.
|
|
- 30” wide new vented enclosure is required when 800A vertical mounted TM type 3VA (3VA55) main breaker is selected in P3.
|
|
|
|
New 30 inches Wide Vented Enclosure for P3 Panelboards Specifications:
|
|
- New 30” wide vented enclosure is available for P3 panels only from the current release.
|
|
- New 30” wide vented enclosure is available as NEMA 1 type enclosure only from the current release.
|
|
- New 30” wide vented enclosure has only two box sizes: 68”H and 80”H.
|
|
- New 30” wide enclosure catalog numbers
|
|
|
|
|
|
- No box modification or box size change with new 30” wide vented enclosure
|
|
- No side gutters to be added to new 30” wide enclosure.
|
|
- COMPAS quote line for the new 30” wide vented enclosure will be type matched and drive to one of above standard enclosure catalog numbers.
|
|
- No N3R type enclosure or N4X type enclosure for 30” wide enclosure as the current release.
|
|
400A and 600A Frames 3VA Breakers offer in P3, P4, P5
|
|
3VA Breaker Specifications:
|
|
- Trip Unit Type: Thermal-Magnetic (TMTU) and Solid State (ETU).
|
|
- Breaker Frames: 400A and 600A.
|
|
- Breaker Types: Thermal-magnetic Trip 3VA53 (400A Frame), 3VA54 (600A Frame).
|
|
Electronic Trip 3VA63 (400A Frame), 3VA64 (600A Frame).
|
|
Electronic Trip 100% Rated 3VA63 (250A Sensor only), 3VA64 (400A Sensor only).
|
|
- Poles: 3VA53, 3VA54 2-Pole in 3-Pole Frame , 3-Pole.
|
|
3VA63, 3VA64 3-Pole.
|
|
- Breaker Lugs Selection: COMPAS UI selections includes the following, in both Al type or Copper Only type, but may be limited to fewer options based on the breaker trip unit type selection or 100% rated option.
|
|
|
|
|
|
- (1)#1-600Kcmil with Control Tap
|
|
- (2)2/0-600Kcmil with Control Tap
|
|
|
|
P3 Panel with 400A and 600A 3VA Offer Specification:
|
|
- Main: 400A or 600A Main in P3.
|
|
- Branch: 400A or 600A sub-feed breaker in P3.
.
- Breaker Mounting : Horizontal mounted
|
|
- Branch Quantity: Quantity (1) 400A horizontal mounted 3VA sub-feed breaker or quantity (1) 600A horizontal mounted 3VA sub-feed breaker in P3
|
|
- Since no design for 30” wide N3R type enclosure in P3, horizontal mounted 3VA breakers, either main or a sub-feed breaker can only be done in P4 or P5.
|
|
- 3VA Breaker Lug Limitation: maximum cable size allowed is either (1)600Kcmil or (2)500Kcmil in P3.
|
|
- Acknowledgement Message: an acknowledgement message is displayed as a conflict in the current release. A checkbox Breaker Flag in conflict resolution
|
|
window can be checked to remove the red after the user sees the information about maximum cable size in P3.
|
|
- P3 800A MLO, mechanical lug with lug size of (3)500Kcmil, no horizontal mounted 400A or 600A 3VA sub-feed breaker allowed or panel type can be changed to P4 or P5.
|
|
- When P3 main is a Sentron JD or LD type breaker, sub-feed breaker can be used is JD sub-feed, no 3VA sub-feed can be selected as the current design.
|
|
- P3 400A or 600A horizontal mounted 3VA main can have (1) horizontal mounted 400A 3VA sub-feed breaker or (1) horizontal mounted 600A 3VA sub-feed breaker.
|
|
- No SEM3 option to be available to 400A and 600A frame 3VA breakers in P3 as the current P3 SEM3 design.
|
|
- P3 Enclosure Type Restriction: when 600A 3VA main and / or a 600A 3VA sub-feed breaker selected in a P3 panel, it requires the new 30” wide vented enclosure.
|
|
- No changes for current P3 logics of vertical mounted 400A or 600A 3VA main breaker configurations.
|
|
P4 and P5 Panel with 400A and 600A 3VA Offer Specification:
|
|
- Main: 400A or 600A main in both P4 and P5.
|
|
- Branch: 400A or 600A branch breaker(s) in both P4 and P5.
|
|
- Horizontal Mounted main and or branch breaker(s) in both P4 and P5.
|
|
- 3VA Breaker Lug Limitation: maximum cable size allowed in P4 is 500Kcmil per phase (when using 600kcmil lugs).
|
|
- If 600Kcmil lug size is required, Panelboard needs to be changed to P5 panel.
|
|
- Acknowledgement Message: an acknowledgement message is displayed as a conflict in the current release.
|
|
A checkbox Breaker Flag in conflict resolution window can be checked to remove the red after the user sees the information about maximum cable size in P4
|
|
- SEM3 option: SEM3 Device option is not available on 600A 3VA main breakers in a power panel. This option can not be selected in both P4 and P5.
|
|
|
|
New Addition 800A Frames 3VA Breakers Offer in P3
|
|
3VA 800A Breaker Specifications:
|
|
- Trip Unit Type: Thermal-Magnetic (TMTU) and Solid State (ETU)
|
|
|
|
- Breaker Types: Thermal-magnetic Trip 3VA55 (800A Frame)
|
|
Electronic Trip 3VA65 (800A Frame)
|
|
Electronic Trip 100% Rated 3VA65 (250A Sensor only)
|
|
- Poles: 3VA55 2-Pole in 3-Pole Frame, 3-Pole
|
|
3VA65 3-Pole
|
|
- Breaker Lugs Selection: COMPAS UI selections includes Al type lugs only, lug size options limit to fewer with 100% rated breaker.
|
|
|
|
|
|
- (4)4/0-500Kcmil Al or (4)4/0-350Kcmil Cu (copper cable)
|
|
|
|
|
|
- (4)4/0-500Kcmil Cu/Al (100% rated) or (4)4/0-350Kcmil Cu (copper cable) for 100% rated
|
|
- (4)4/0-600Kcmil Cu/Al (100% rated)
|
|
|
|
P3 Panel with 800A 3VA Offer Specification:
|
|
- Main: 400A or 600A main in P3.
|
|
- Vertical mounted main in P3.
|
|
- 800A TM type 3VA55 main breaker requires new 30” wide vented NEMA 1 type enclosure.
|
|
- 800A ETU type 3VA65 main breaker can still fit in current 24” wide enclosure per design.
|
|
- SEM3 option: No SEM3 Device option on 800A Main breakers as the current P3 design.
|
|
Technical
|
|
|
|
- Price Version / Release Date: 202100419 / 4-2021
|
|
BT Twin Tandem Breakers Available in P1
|
|
BT Breaker Specifications:
|
|
- Breaker Series: BL Tandem/Twin called "BT" series
|
|
- Breaker Voltage: 120/240VAC
|
|
- Interrupting Rating: 10KAIC, 22KAIC
|
|
- Trip Unit Type: Thermal-Magnetic
|
|
- Breaker Trips: Two 15A or two 20A circuits, 15-15A or 20-20A
|
|
|
|
B2020
|
|
B1515H
|
|
B2020H
|
|
- Panel Type: BT breakers are only available to P1 panels in the currently release.
|
|
- Breaker Space: BT breaker takes up one inch unit space or one pole space in P1
|
|
- BT Quantity: 18 circuits P1: up to (10) BT breakers
|
|
30 circuits P1: up to (20) BT breakers
|
|
42 or more circuits P1: up to (30) BT breaker
|
|
- BT Accessories: Padlock or red padlock options are available to BT twin breakers
|
|
- Unassembled Panelboard Offer: UPB option for BT breakers in P1 is available with the current release
|
|
- Configuration UI: BT Twin Tandem is under Device list in UI, on SECTION/MAINS page
|
.
|
Russelectric ATS
|
|
Selectors
|
|
- Remove XF8 default based on BTDR selection
|
|
Power Connections
|
|
- Set default Emergency power connection for bypass switches to be Rear Top
|
|
- Changed “Normal” connection to “Source 1”
|
|
- Changed “Emergency” connection to “Source 2”
|
|
- Additional combinations of connections enabled for open style transfer switches
|
|
Lights
|
|
Changed default light type from LEDTRONICS to Idec Mini LED for Annunciators
|
|
Miscellaneous Accessories
|
|
|
|
Pricing
|
|
- Updated PBR accessory to $550 list price for all configurations
|
|
|
|
Russelectric LV/MV SWG
|
|
WL Breaker
|
|
- Optional Fuse Amperage enabled to fix bug preventing users from selecting 150kA & 200kA breaker configurations
|
|
- Allow for manual selection of breaker voltage when “Special” system voltage is selected for lineup
|
|
|
|
Russelectric SWG Mods
|
|
Pricing
|
|
- Corrected list price calculation from initial implementation
|
|
Custom Component
|
|
- Common custom part #s added that will fill in all required fields for the custom component instance based on a lookup table
|
|
|
|
Russelectric ATS Mods
|
|
Labor Summary Tab
|
|
- New labor summary tab added to provide capability for adding engineering, production, programming, and field service labor hours
|