Warning: preg_match_all(): Compilation failed: invalid UTF-8 string at offset 81 in D:\xampp\htdocs\client\inc\DocumentParser.php on line 262
COMPAS Go Release : July 2021 - Publish Sandy Articles
Sandy FAQ

COMPAS Go Release : July 2021


This articles details the information on the knowledge base releases for the month of July 2021. 

Russelectric

Switchboard

Panelboard

LVS / RCS

Components


.


.

3VA

  • Select technical review required when motor operator is selected

Drawing notes

  • Correct enclosure type text for CA Type 2 and sprinkler proof options

  • Correct certification text when CA options selected

Enclosure

  • Remove N3R + Gasket�s option (standard N3R already includes gaskets)

  • Allow selecting Sprinkler Proof / Type 2 when NEMA 1 only

 

Estimate Sheet / Proposal

  • Add missing prices for 3VAs with motor operator & key interlock

  • Add BPS manufacturer to the price description text

  • Add pricing for TPS4 SPD

  • Submittal improvement project updates � Update proposal/estimate sheet device descriptions & text

MCCB Mapping

  • Add parallel breaker default table for Canadian configurations, to prevent selection of 400 & 600A 3VA breaker when CA.

Senton MCCB

  • Remove incorrect option for 100% rated SPD breaker

  • Remove SZSI selection

Series Ratings

  • Updates for load centers

SMM/MMS

  • Prevent selecting SMM/MMS when CSA selected

SPD

  • Add TPS4 SPD (US only)

Switchboard

  • Change �CA Options� selection to � �CSA � Canadian Options�

  • Change CA Regional code selections: �Eastern� to �East� and �Western� to �West�

Utility Metering

  • Add Toronto Hydro & Epcor Power Edmonton (23 CA utilities are now selectable)

WL Breaker

  • Default to FS2 when EUSERC pull or CA Options selected

Technical

  • KB Version: 01.01.56.01

  • Price Version: 20190111

  • Release Date: 7/2021

.

Panelboard KB New Enhancement and New Features

P5 New 32� Wide Section Width

  • New P5 32� wide section, is available in COMPAS Panelboard configurator, compare to P5 with 38� width section

  • A new UI checkbox, P5 32� Wide, is on Panel Type UI, next to Distribution Panel selection  

  • New P5 32� wide section will be the default if the configuration qualifies for

  • P5 32� wide and P4 share most of common or the same offers and features, except a few where P5 features take place

    • P5 Dead Front

    • P5 Section Depth

    • P5 Breaker Strap Kit

 

  • P5 32� wide section main breaker rating is limit to 800A frame

  • P5 32� wide SEM3 offer: the same as the current P4 offers

  • Main VBS and Main HCP: not offered in P5 32� wide section, the same as the current P4 design

  • New P5 32� width section dimensions: 

  • NEMA 1 enclosure:  32� W x 12.75� D x (60� or 75� or 90�) H

  • N3R or N3R/12 outdoor:   32� W x 14.5� D x (60� or 75� or 90�) H

  • New P5 32� wide NEAM1 Indoor enclosure catalog numbers:

    • US2:PB860T32

    • US2:PB875T32

    • US2:PB890T32

  • New P5 N3R or N3R/12 outdoor enclosure catalog numbers:

    • US2:WPS860R32

    • US2:WPS875R32

    • US2:WPS890R32

  • New vented and unvented front catalog numbers are also offered

  • NEMA 4X box option is not available for P5 32� wide

  • NEMA 1 special front options will be available in upcoming COMPAS release

  • All P4 panels are qualified to be converted to new 32� wide P5

  • All saved or existing P4 panels, change order P4s can remain as P4 panels when reconfigure, but they can also be converted to P5 32� Wide

New SPD TPS4 Family Is Available to Power Panels

  • New TPS4 SPDs are available to power panels, P4 and P5

  • New TPS4 SPD will be the default SPD in the new power panel configurations

  • COMPAS user has the option to change TPS3 SPD to TPS4 SPD in power panels

  • SPD Configuration UI option change

  • SPD Model (previously) is changed to TPS Family (new option) 

Panelboard KB Improvements, Corrections and Fixes

  • P3 panels with 200% Neutral option, Feed Thru Lug option and sub feed breakers option rules updated per the latest P3 designs

  • 3VA41 breakers are visible when 100A main ampere selected

  • COMPAS report showing Al/Cu text descriptions for all 3VA breakers lug description

  • BT breaker pole selection update: 2 and 3 pole selections are no longer visible in UI

  • BT breaker is listed next to or under Breaker in Device list

  • Digital Meter configuration UI updates

  • Panelboard Layout Improvements, Corrections, and Issues Fixes:

  • P2 panels 600A MLO with 2-pole 3VA41 breakers

  • P3 panels 30� wide section with 400A / 600A 3VA sub feed breaker

  • P4 / P5 configurations with split bus or branch contactor

  • P3 with split bus configurations layout updates

Technical Info

  • KB Version:   01.01.79.06

  • Pricing Version:  20210714

  • Release Date:  7/2021

.

Custom Component

  • Fixed calculation bug associated with $0 material cost, 0 labor hours, or 0 wire points.

Drawing Modifications - HRG

  • Add symbol for Siemens HRG to Front View and One Line

Drawing Modifications - One Line

  • Add Lug Quantity for Cable Tap Incoming

  • Add Neutral for Cable Incoming or Transformer Incoming.

  • Add Bonding Jumper for Cable Incoming or Transformer Incoming.

  • Add compartment reference on One Line.

  • Modify Transformer Incoming symbol in preparation for future USS enhancements.

Technical Info

 

  • KB Version: 00.00.45.01

  • Price Version: 20121101

  • Release Date: 7/2021

.

Russelectric ATS

Timers/Relays

  • TDNP & TDNNP required for Closed Transition switches

Service Entrance

  • No service entrance available for wallmount configurations

  • Bypass & 4000A configuration only allow service entrance in separate cubicle

Russelectric ATS Mods

Switch Serial #

  • Fixed bug with NA value input

Russelectric LV/MV SWG

Breakers

 

  • Neutral CT auto selecting for 4 wire lineup configurations

  • Refined trip unit & ground fault rules for SqD breakers

Technical Info

  • KB Version:  00.00.05.02 [ATS,ATS Mods] / 00.00.03.01 [LV/MV SWG]

  • Pricing Version: -

  • Release Date:  7/2021

.

Lighting & Heating Contactor

  • Mechanically Held CLM with no Disconnect

  • 30 Amp and 60 Amp versions 6-12 poles

  • These versions will be routed to our vendor for sourcing instead of routing to the South Haven Mod Center

  • No change in the features or options available.

Transformer

  • Standard Dry Type 480V:208Y/120V 15-750 KVA 3F3YxxxFD16 (115 C Temp Rise) and 3F3YxxxBD16 (80C Temp Rise) will now default to Series A sourced versions.  

  • These versions are not Seismic Rated this time

  • Users may continue to select Override Series J or H if needed to meet specific technical requirements.

Breaker WL

  • Configurator updated to allow reverse configuration (manually entering the 15digit catalog number) when the breaker is provided with an EMC Filter on the Electric Trip Unit.

Technical Info

 

  • KB Version:   LHcontactor - 00.00.09.24, Breaker_WL - 00.00.00.28, Transformer - 00.00.06.29

  • Pricing Version:  LHcontactor - 20210401, Breaker_WL - 20210401, Transformer - NA

  • Release Date:  7/2021