This articles details the information on the knowledge base releases for the month of November 2021.
.
|
|
|
|
|
|
|
|
Panelboard
|
Switchboard
|
MCC
|
LVS / RCS
|
Russelectric
|
|
.
Panelboard
|
3VA Breaker Updates
|
|
New Twin Mounted 3VA 400A / 600A Breakers in P5
|
|
- Horizontal twin mounted 400A and 600A 3VA breakers are available in P5, in addition to the current single mounted option
|
|
- Standard P5 38 wide section only
|
|
- 3VA breaker types can be twin mounted: 3VA53, 3VA63, 3VA54, 3VA64
|
|
- New UI option for Breaker Mounting in COMPAS Panelboard configurator when a P5 38 wide section is configuring
|
|
- Default breaker mounting option for 400A / 600A 3VA:
|
|
|
|
- Twin mounted 3VA 400A breakers can be placed in standard 38 wide P5 section
|
|
- Twin mounted 3VA 600A breakers can only be placed in 46 wide P5 section
|
|
- Twin mounted 3VA 400A breakers with SEM3 option requires 46 wide P5 section
|
|
- Twin mounted 3VA 600A breakers with SEM3 option cant be done in P5. This can be configured in Switchboard product
|
|
- Unit space height: twin mounted 400A / 600A breaker kit height is 6.25
|
|
- Twin mounted option is not available for P4 or P5 32 wide section
|
|
- Twin mounted 400A 3VA breakers restrictions in P5:
|
|
- Maximum cable size for twin mounted 400A is (2)250Kcmil
|
|
- If 600Kcmil lug is required, change section width to 46 wide
|
|
- SEM3 device option on twin mounted 3VA 400A breakers require section width of 46
|
|
- Twin mounted 600A 3VA breakers restrictions in P5:
|
|
- Twin mounted 600A 3VA in P5 require 46 wide enclosure
|
|
- Twin mounted 600A breakers with SEM3 option cannot be done in P5
|
|
- Panel lead time for P5 with twin mounted 400A or 600A 3VA breakers:
|
|
- Addition 20 days adder for a P5 with twin mounted 400A and 600A 3VA breakers
|
|
|
|
3VA Series Rated Updates
|
|
- KB updates for 3VA series rated offers
|
|
|
|
P3 800A 3VA Main Breaker Updates
|
|
- P3 panels with 800A 3VA main breakers, either 3VA55 or 3VA65, will not have an option of a Sentron 400A JD type subfeed breaker
|
|
|
|
Sentron & VL Breakers Updates
|
|
- New UI informational text note for Sentron ED breakers with Ground Fault Sensing Kit option
|
|
- Power panels with VL D frame branch breakers (ND, HD, LD), SME3 option and compression lug require 46 wide section width
|
|
|
|
Panelboard KB Other Enhancements
|
|
- All P4 panels will require Tech. Review from November COMPAS release as per future P4 phase out preparation
|
|
- Users can start the process of converting P4 panels to either P3 or P5 with 32 wide section if they want to bypass Tech. Review process
|
|
- Special locks option rules are updated:
|
|
- Lighting panels: special lock option is removed with N3R outdoor or NEMA 4X enclosure
|
|
- Power panels: special lock option is removed with NEMA 4X enclosure
|
|
- Power panels with 200/200A, 400A, and 600A VBS require custom design enclosure, no standard box catalog number will be generated in COMPAS order line
|
|
- KB rules updates for custom interior design settings
|
|
- Series rated updates for non-3VA breakers
|
|
- Power panels breaker pricing adjustment
|
|
|
|
Technical Info
|
|
|
|
- Pricing Version: 20211101
|
|
|
..
Switchboard
|
3VA
|
|
- Add 400 & 600A panel, twin mount
|
|
- 400A will default to twin mount and 600A will default to single mount, with manual option for twin
|
|
|
|
Pricing
|
|
- Update special bracing ATS text
|
|
- Add WL certification type to description
|
|
|
|
Series Ratings
|
|
- Add latest 3VA series ratings
|
|
|
|
Technical Info
|
|
|
|
|
|
|
.
MCC
|
- Added PAC3120, PAC3220 digital meter to replace PAC3100, PAC3200
|
|
- Added 100 percent rated circuit breaker unit option to unit schedule drawing
|
|
- Added characteristic Factory Option Number
|
|
- HE breaker is no longer allowed for everything except feeders
|
|
- Dual FCB unit over sizing rules are now calculating properly
|
|
- Handle aux. switch is no longer allowed for SIERS units
|
|
- NEMA 3R door fan is no longer allowed for other than NEMA 3R
|
|
- Changed vertical bus end Y for top 800-1200A MCB, FCB with neutral transformer
|
|
- Unit only panelboard now has Non Space Fixed Units Count = 1 not 0
|
|
- Product Hierarchy in SAP now has 562SIXXXX-AJKA0019 not 562SIXXXX-AJKA0045 for an A5 option code unit only for order 3009127381-23000
|
|
|
|
Technical Info
|
|
|
|
|
|
|
.
LVS / RCS
|
One Line Drawing Updates
|
|
- Adding Lug Details for Cable Feed Incoming
|
|
- Modify Busway drawing symbol; adding Busway Neutral, Ground, and Bond Jumper.
|
|
Note: Select Neutral Thru Bus Type = Thru Neutral for Busway Application
|
|
|
|
Technical Info
|
|
|
|
|
|
|
.
Russelectric
|
Russelectric ATS
|
|
Standard Drawings
|
|
- Added compression lug configuration availability on standard elevation drawings in Submittal Package tool
|
|
Power Connections
|
|
- Ground & Neutral configurations moved under each source instead of separate group boxes
|
|
- Neutral option to match source available
|
|
Enclosure
|
|
- Bypass Access selection enabled for Type 4 & Type 12 enclosure ratings
|
|
- Padlocking always provided on 3R, 4, 4X enclosure ratings
|
|
Accessory rule refinement
|
|
- Elevator Contacts description update
|
|
- If XF7, XK7, or XP7 selected then the following accessories are not all available: XK3, XL3, XF8, XK8, XP8, XC8, TDPS, BTDR
|
|
- LT23 only available on annunciators
|
|
- If XP8, XF8, or XK8 are selected, then XK3 and XL3 not available. (and vice versa)
|
|
- When CMES is selected, then CMESO is not available (and vice versa)
|
|
- CMESO and CMES quantities limited to the quantity of CES contacts selected
|
|
|
|
Russelectric LV/MV SWG
|
|
Competitor Breaker
|
|
- Fixed bug in configuration of trip units on Schneider breakers
|
|
|
|
Technical Info
|
|
- KB Version: Russelectric ATS [00.00.09.01], Russelectric ATS Mods [00.00.09.01], Russelectric LV/MV SWG [00.00.07.01], Russelectric SWG Mods [00.00.08.01]
|
|
|
|
|