|
|
How to install auxilary switches for a WL breaker?
1. Auxiliary switches (contacts) snap into a location immediately to the right of the charging handle. Make sure both the upper and lower tab on the switch housing are snapped into the corresponding location in the breaker.
2. Connect the wires to appropriate terminals (X5 or X6) by inserting a narrow-bladed screwdriver (3mm) into the rectangular opening and levering gently upwards until the wire can be inserted. Note that the leads are hot-stamped with the correct terminal number. This video is meant only to enhance, not replace, the operating instructions enclosed with every product. Please review all instructions carefully before viewing the video. Product instructions are subject to technical changes without prior notice.