Warning: preg_match_all(): Compilation failed: invalid UTF-8 string at offset 81 in D:\xampp\htdocs\client\inc\DocumentParser.php on line 262
How to retrofit the automatic reset? - Publish Sandy Articles
Sandy FAQ

How to retrofit the automatic reset?


1. Remove tripping solenoid F5 from ETU.

2. Place spring lock washer on retaining pin.

3. Insert reset spring.

4. Slide retaining pin into place to secure reset spring.

5. Lock retaining pin in place with 2nd spring lock washer.

6. Press bracket of reset spring down.

7. Insert tripping solenoid F5 back in to ETU. This video is meant only to enhance, not replace, the operating instructions enclosed with every product. Please review all instructions carefully before viewing the video. Product instructions are subject to technical changes without prior notice.

This article was: