Can I have an infrared viewport in my arc resistant low voltage switchgear?


Yes, provided the viewing pane used meets the minimum requirements listed in the Siemens LVS UL file, an infrared view-port is allowed in WL arc resistant LVS.

The infrared view-port used as a standard in WL LVS meets all the UL minimum requirements. Other view-port manufacturers would have to be evaluated on a case-by-case basis.



Article ID: 1009
Last updated: 30 Mar, 2021
Revision: 5
Product Information -> Can I have an infrared viewport in my arc resistant low voltage switchgear?
https://sandy.compas.siemens-info.com/can-i-have-an-infrared-viewport-in-my-arc-resistant-low-voltage-switchgear_1009.html