What are the required clearances around Siemens WL arc resistant low voltage switchgear?


The minimum required space around the equipment is 39” in the front, 36” in the back and sides and 118” from floor to ceiling (120” from floor to ceiling for arc resistant WL LVS with optional exhaust ductwork).