DAS (Dynamic Arc Flash Sentry)
|
NEC 240.87
- Energy-reducing maintenance switching with a local status indicator
- An energy-reducing maintenance switch allows a worker to set a circuit breaker trip unit to instantaneous while the worker is working within an arc flash boundary as defined in NFPA 70E, and then to set the trip unit back to a normal setting after the potentially hazardous work is complete.
|
Standard DAS – WL & Sentron Breakers
|
- One DAS system per WL Breaker (ETU776 trip unit required)
- (4) Sentons w/ DAS in 7.5” Auxiliary compartment
- (5-6) Sentons w/ DAS in 10” Auxiliary compartment
- (7-8) Sentons w/ DAS in 15” Auxiliary compartment
- Each breaker has it’s own independent DAS setup
- One Light & Switch per breaker
- Standard mount with lights & switch in DAS auxiliary compartment
- Custom option to supply for customer to mount remotely
- Auxiliary compartment in same or adjacent section required for each WL
- SB2 or SB3 with custom auxiliary compartments
- Use on mains and/or branches
|
Standard DAS – WL Breakers
|
- DAS may be unselected on device if not required
- If an auxiliary compartment is already configured on device, use Existing DAS
- Compartment will remove the automatically created DAS compartment
- Meters / SPDs can be added to the automatically generated DAS compartments
|
Standard DAS – Sentron Breakers
|
VL breakers will default… you must manually select a Sentron type breaker
- Select Solid State Trip Unit
- Select Sentron type from list (Format = SxxD6 @ ##K)
- Select Frame amperage from list
DAS Defaults when >= 1200A / Optional when < 1200A
|