Wire size range of the EGK / ECGK / IGK / ICGK lug connections/holes:
(note: The multiple combinations typically only apply when used as an equipment ground.
If similar bar is used as a neutral bar, only one wire can be used in each hole.)
EGK / ECGK / IGK / ICGK Installation Instructions:
Ground bus to be mounted in either left or right gutter with hardware provided. Applied torque ratings shall be 45-lbs-inch for three No. 10 AWG solid copper conductors in the large holes. For all other combinations of conductors, refer to the torque rating label on the panelboard.
Note: For IGK/ICGK, insure ground bar is attached to Glastic insulator with 2 screws before mounting insulator to enclosure. Ground Bar mounts thru side holes oriented as shown in picture below.
This chart is on labels for P1, P2 and P3 Enclosures.
.png)
EGK / ECGK kit parts:
.png)
IGK/ ICGK kit parts
.png)
See link below for Web Page where document can be downloaded: click here
Additionally, the factory can provide some custom solutions when needed. Contact Spartanburg Customer Support for more information.