Wire size range of the EGK / ECGK / IGK / ICGK lug connections/holes:
(note: The multiple combinations typically only apply when used as an equipment ground.
If similar bar is used as a neutral bar, only one wire can be used in each hole.)
EGK / ECGK / IGK / ICGK Installation Instructions:
Ground bus to be mounted in either left or right gutter with hardware provided. Applied torque ratings shall be 45-lbs-inch for three No. 10 AWG solid copper conductors in the large holes. For all other combinations of conductors, refer to the torque rating label on the panelboard.
Note: For IGK/ICGK, insure ground bar is attached to Glastic insulator with 2 screws before mounting insulator to enclosure. Ground Bar mounts thru side holes oriented as shown in picture below.
This chart is on labels for P1, P2 and P3 Enclosures.
EGK / ECGK kit parts:
IGK/ ICGK kit parts
See link below for Web Page where document can be downloaded: click here