Can an AFCI circuit breaker be used on a 208Y/120v 3 phase 3 wire system?


A single pole AFCI circuit breaker can be used on a 120v circuit derived from a single leg of a 208/120v. A two pole AFCI circuit breaker can be used on a shared neutral circuit between two adjacent 120v circuits.

The two-pole CAFCI is intended for a different use than most two-pole circuit breakers. This CAFCI is intended to allow contractors to use multi-wire branch circuits (commonly known as "shared neutrals") which helps save on installation costs. It is intended for use on two single-pole, 120Vac circuits. In fact, at the time of this print, there is not even a safety standard written that defines the requirements for AFCIs in 240V applications.

Please see attached documentation for more information on the use of two pole AFCI circuit breakers.