How to connect a handheld test device for a WL breaker?
1. Ensure the breaker is in the disconnected position.
2. Make note of the setting values of the trip unit.
3. Remove connection cover at bottom of ETU.
4. Switch off ground-fault protection, setting value IR=1.0*In.
5. Connect handheld test device to ETU.
6. Connect power supply to handheld test device.