How to retrofit the shutter for a WL breaker?
1. Assemble the actuator and complete it with the spring; insert the actuator.
2. Attach the spring to the frame.
3. Latch the shutter in the actuator.
4. Screw the shutter in place.
5. Test the functionality of the shutter. Note: Update options label; Install guide frame in switchboard.