Warning: preg_match_all(): Compilation failed: invalid UTF-8 string at offset 81 in D:\xampp\htdocs\client\inc\DocumentParser.php on line 262
What does the "test " button actually test on the WL ETU trip unit? - Publish Sandy Articles
Sandy FAQ

What does the "test " button actually test on the WL ETU trip unit?


Pressing test button on the WL family of trip units provides a wide array of check functions to validate the health of the trip system, and the ability of the circuit breaker to trip.  These include:

  • Initiating self diagnostic tests on internal circuits “L" (long time trip pickup and delay), "S" (short-time pickup and delay), "I" (instantaneous pickup), and "G" (ground-fault pickup and delay) if installed (ground-fault protection is optional, and may not be included)
  • Illuminates LEDs on trip unit to determine whether the LEDs are functioning
  • Verify and test the installed rating plug
  • Check communication between the circuit breaker's identity module and the trip unit , and
  • Perform limited testing on the Rogowski current sensors

This testing can be performed with or without tripping of the circuit breaker.  For more detail on performing internal self-tests, see Chapter 9 of the WL Operator's Manual.  

The latest versions of the WL Operator's Manuals can be found at: 