What if any Low Voltage Switchgear options aren't available in Type WL arc resistant Low Voltage Switchgear?


The following low voltage switchgear options aren't available in arc resistant construction – drip hood, pull box, and two-piece breaker doors.

Floor plates are available but they are a special design for arc resistant LVS and go on the bottom of the sill channel.

They can't go on the switchgear frame like normal floor steel since they would block the plenum in the sill channel and void the arc resistant rating.