This is the internal self-test function of the trip unit functions. Test can be done with or without tripping the circuit breaker.
To test without tripping, press “TEST.”
To test with tripping:
- Press both the “TEST” and “CLEAR” buttons at the same time and hold for at least 10 seconds
- Release both at the same time
For more information about testing WL circuit breakers, check out Chapter 9 of the WL Operator’s Manuals.