Warning: preg_match_all(): Compilation failed: invalid UTF-8 string at offset 81 in D:\xampp\htdocs\client\inc\DocumentParser.php on line 262
COMPAS KB Release : July 2022 - Publish Sandy Articles
Sandy FAQ

COMPAS KB Release : July 2022

This article details the information on the features and bug fixes released as part of COMPAS knowledge base. Following are released for the month of July 2022. 

. 


Switchboard

3VA Breakers

  • Update communications settings to show ModBus TCP as native communications protocol

  • Allow selecting ModBus TCP + additional communications protocol

  • Update 3VA55/3VA65 as default 800A MCCB for US applications

  • Allow selecting 400A incoming with 600A frame/400A trip 100% rated main, or 600A incoming with 800A frame/600A trip 100% rated main

Incoming

  • Remove technical review required when 1000A incoming and main with 1000A trip setting

IPS Cutoff

  • Prevent selection of 3VA41

Proposal

  • Show lightning arrestor on proposal (previously only shown on estimate sheet)

SMM/MMS

  • Add 3VA61, 3VA52, 3VA62 as MCCB selections

Switchboard

  • Default selection of Standard DAS for new configurations

Utility Metering

  • Allow Cold sequence for Central Maine utility

  • Add Umatilla Electric Co-op to EUSERC utilities

Technical Info

  • KB Version: 01.01.64.01

  • Price Version: 20220401

  • Release Date: 7/2022

.


SIEBREAK

Adjustments to the existing features: 

  • New value options for “line cable quantity” and “load cable quantity” in LIS, VCB, and AUX units

      Values detailed in the following tables…

  • Maximum quantity of cables per phase for rear access LIS and VCB units

  • Maximum quantity of cables per phase for front access (56”D) cable pull and rear access cable pull

.


Russelectric

Russelectric ATS

Switch Information

  • Annunciator type added – PLC vs Hard wired

  • Annunciator Complexity update

  • Fixed bug - LT23 pricing only 1 per Annunicator

Contacts

  • MMR complexity update

Miscellaneous

  • RTSCD Service Entrance available

Russelectric ATS Mods

RPTCS Upgrades

  • Accessories standard to the RPTCS controller will now populate regardless of serial # database lookup

Russelectric LV/MV/CNTRL SWG

WL Breaker

  • Non-automatic breaker type now available

Digital Meter

  • Removed 9610 & replaced PAC3100/PAC3200 with PAC3120/PAC3220

Reports

  • Custom component description fixed for control switchgear

Russelectric SWG Mods

Digital Meter

  • Removed 9610 & replaced PAC3100/PAC3200 with PAC3120/PAC3220

Technical Info

  • KB Version: Russelectric ATS [00.00.15.01], Russelectric ATS Mods [00.00.15.0], Russelectric LV/MV/CNTRL SWG [00.00.13.01], Russelectric SWG Mods [00.00.12.01]

  • Price Version: 20220406

  • Release Date: 07/2022

.


Components

Molded Case Circuit Breakers

  • Naval rated (UL 489 Supplement SB ) versions of 3VA5 (Thermal Magnetic) and 3VA6 (Electronic Trip Unit) are now identified in the configurator

  • Note that 3VA6 breakers are naval rated for standard electronic breakers but not for 100% rated breakers

Lighting and Heating Contactors

  • Configured LH contactors that include factory modifications for Timers – T7, T8, T9 will have these order lines routed to our panel shop for manufacturing
This article was: