This is the internal self-test function of the trip unit functions. Test can be done with or without tripping the circuit breaker.
To test without tripping, press “TEST.”
To test with tripping:
For more information about testing WL circuit breakers, check out Chapter 9 of the WL Operator’s Manuals.
The latest versions of the WL Operator's Manuals can be found at:
UL 1066 WL Circuit Breakers: Click here
UL 489 WL Circuit Breakers: Click here