Can the Sirius Act line of pilot devices be submerged under water?
Sirius Act pilot devices cannot be operated or used under water.
Views: 11266
Comments: 0
Can the TA2J630 lug be used on the JXD6 circuit breaker?
The TA2J630 lug is not listed for use on the JXD6 series of circuit breakers. It is approved for use on the Sensi trip version of the breakers such as the SJD6 or SHJD6
Views: 11294
Comments: 0
Can the trip unit be changed on an FXD6 circuit breaker?
No, the "X" in the part number indicates a non-interchangeable trip unit. If a different trip unit is needed, the entire circuit breaker would need to be replaced.
Views: 11288
Comments: 0
Can the VL trip units be replaced in the field?
Provided the VL breaker is an interchangeable trip unit, the trip units can be replaced in the field. Some versions of the breaker are listed as non-interchangeable...
Views: 11290
Comments: 0
Can we install motorized operator on enclosed circuit breaker?
Electric motor operators are usually mounted on the face plate of the breaker which increases the total depth of the breaker, and it won’t fit in Siemens standard...
Views: 10892
Comments: 0
Can you convert a non-automatic WL Breaker into an automatic WL Breaker or vice-versa?
No. It is not possible to convert a WL breaker (with trip unit) to a WL non-automatic switch (without trip unit). Likewise it is not possible to convert a WL...
Views: 11294
Comments: 0
Can you mount a QT frame tandem breaker in a full circuit G3030 for ex loadcenter?
NO. QT breakers are not listed as approved breaker for the G3030 or any other full circuit Load Center. He said he can install a mini(tandem) with a "U" suffix and...
Views: 11470
Comments: 0
Does the WL Breaker handheld test set (WLTS) need to be calibrated periodically ?
The simple answer is NO. Because the WL trip units are numeric and not analog, and because there is only one type of current sensor per frame size, the requirement...
Views: 11317
Comments: 0
Do the VL circuit breakers have replacement handles?
Siemens does not offer replacement handles for the VL breaker family. The VL breaker is constructed as an integral unit and if the cover is removed, the operation of...
Views: 11309
Comments: 0
Do you ECPLD3 padlocking device works on a 3 pole breaker with a shunt-trip?
No, the ECPLD3 is a 3 pole padlocking device. We don't have a padlocking device that it will work with a 4 pole breaker.
Views: 11307
Comments: 0