What is the minimum load current that the WL breaker will display?
The WL trip unit has a default “Underflow Limit” of 50A. This means that for loads less than 50A, the display will always show zero current flow. The underflow limit...
Comments: 0
What is the life expectancy of WL LVS?
The answer to the ? is “it depends”. If WL LVS is properly applied and maintained, there isn’t any reason it can’t see a 35+ year life expectancy. A good maintenance...
Comments: 0
Integral Ground vs. Housing Ground
The internal ground bar on standard feeder and plug in sections are not intentionally bonded, or isolated, from the housing within a single section of Busway. The...
Comments: 0
What ground fault detection modes does the WL breaker support?
The WL breaker supports residual (3 wire/4 wire) and direct sensing ground fault detection modes. The ground fault selector switch on the ETU745 and ETU748 trip...
Comments: 0
What is the difference between ground fault alarm and ground fault alarm and trip in WL breaker?
Ground Fault Alarm vs. Ground Fault Alarm and Trip The WL ground fault module can be supplied as one of two variants. The first option is an alarm only module. This...
Comments: 0
How to search an approved Metering DB product?
Steps to search for an Utility metering product for given utility company. 1. Go to Product Selector from COMPAS Go. 2. Select Product Selector and then...
Comments: 0
How do I send the Siemens product specification as email or download the specification?
1. Login into the COMPAS Go with valid credentials. 2. Select the Product Catalog from the task menu 3. Click on the Product Catalog, navigates to the...
Comments: 0
What is the standard depth of a switchboard section?
Standard depth of switchboard are listed below. For 1200A and less 20’’ For 1200-2000A 28’’ For 2000-6000A 38’’
Comments: 0
What are all the Bus Plug options for Sentron Busway?
Sentron Bus Plugs can be configured for horizontal or vertical applications. The following Bus Plugs can be mounted (side by side) five (5) per busway side channel...
Comments: 0
How to Information on "Beware of Gray Market Products" (Video 3.41 min)
Gray Market products are purchased through brokers and not the manufacture. No Warranty! To understand the implications of purchasing a Gray Market Product click the...