Can I convert my existing WL low voltage switchgear to arc resistant WL low voltage switchgear?
It is physically possible to convert existing WL low voltage switchgear to the arc resistant design but probably would not be economically feasible to do so. Each...
Comments: 0
What strap kit is used to install a NGB, LGB or HGB breaker in a P4 panelboard?
The catalog number for the strap kit is SNB. This strap kit accepts all ratings allowed in the panelboard and pole configurations. All strap kits are made of copper....
Comments: 0
How do you remove the undervoltage release (UVR) for a WL breaker?
How do you remove the undervoltage release (UVR) for a WL breaker? It is occasionally necessary to remove the UVR either so that the breaker can be closed without...
Comments: 0
What is the proper way to install the interphase barriers and insulating plate on the 3VA 250A circuit breaker?
Click the link below to the information video for details about installing the 3VA 250A interphase barriers and rear insulating plate. Your browser doesn"t support...
Comments: 0
What is the proper way to install the rotary handle operator on the 3VA 250A circuit breaker?
Click the link below to the information video for details about installing the 3VA 250A rotary handle operator. Your browser doesn"t support video. Please...
Comments: 0
How to install a bell alarm on a WL breaker?
How to install a bell alarm on a WL breaker? 1. Remove the trip unit carrier from the breaker. 2. The bell alarm switch mounts on the right side of the carrier as...
Comments: 0
How to install a continuous duty (CD) shunt trip for a WL breaker?
How to install a continuous duty (CD) shunt trip for a WL breaker? 1. Remove bracket which holds the accessories in place. 2. Install the CD shunt trip in the...
Comments: 0
How to install a control gate on a WL breaker?
How to install a control gate on a WL breaker? 1. Hook/secure control gate into place. 2. Test the functionality of the control gate. 3. Fit the spring in place....
Comments: 0
How to install a racking mechanism on a WL breaker?
How to install a racking mechanism on a WL breaker? 1. Fit racking mechanism. (in disconnected position) 2. Insert racking shaft. 3. Insert crank. 4. Secure...
Comments: 0
How to install auxilary switches for a WL breaker?
How to install auxilary switches for a WL breaker? 1. Auxiliary switches (contacts) snap into a location immediately to the right of the charging handle. Make sure...